Telephone & Data
View Telephone and Data Riser Diagrams.
Wall Data Outlets
- 4×4 standard electric box
- Single gang plaster ring
- 1″ EMT conduit w/pull string
- Conduit runs up 6″ above ceiling w/ 90 degree bend and bushing at end
Floor data outlets
- 1″ EMT conduit w/pull string
- 4×4 standard electric box stubbed above floor 6″
- NO FLUSH MOUNTED FLOOR BOXES UNLESS SPECIFICALLY REQUESTED
Overhead Projectors
- 2 each 1″ EMT conduits w/pull strings from floor under podium at front of room to center of ceiling
- 1 each 1″ EMT conduit w/pull string from floor under podium at front of room runs up 6″ above ceiling with 90 degree bend and bushing at end
- 110v duplex outlet attached to structure beside end of conduits in the ceiling, on dedicated power circuit
Feeder Conduits
- Long sweep bends
- Rigid conduit from exterior wall to equipment room
Wiring Closet
- 328′ maximum run to outlet
- One closet per building
Tele/data Equipment Room
- Minimum room size is 8’x8′ (can share space with electric panels, but NOT motors and transformers)
- Sized to allow access to three sides of equipment
- Dedicated power circuits for equipment outlets
- Two service power outlets
- 6″ copper ground buss tied to building ground
- Walls painted
- Floor VCT or sealed
- Ceiling not rigid
- Lighting level for normal tasks
- Temperature control between 55 to 80 F
- No water sprinkler heads in room
- Locate room on middle floor for multistory buildingsĀ (stack vertically)
- Rigid conduit from main panel to outside
- Sleeves through floor to other floor’s subpanels, and from top finish floor to attic
General Note
All wiring, equipment, and cover plates to be provided and installed by Elon.